GSO IEC 60670-24:2014
IEC 60670-24:2011
Gulf Standard
Current Edition
·
Approved on
25 December 2014
Boxes and enclosures for electrical accessories for household and similar fixed electrical installations - Part 24: Particular requirements for enclosures for housing protective devices and other power dissipating electrical equipment
GSO IEC 60670-24:2014 Files
No files for this standard are available in the store currently.
Obtaining this standard through the store is currently unavailable. You can acquire it directly from its source.
GSO IEC 60670-24:2014 Scope
Replacement:
This part of IEC 60670 applies to enclosures and parts of them for housing protective devices
and other power dissipating electrical equipment intended to be used with a rated voltage not
exceeding 400 V and a total incoming load current not exceeding 125 A for household and
similar fixed electrical installations.
These enclosures are intended to be installed where unskilled persons have access. They are
intended to be integrated with electrical equipment on site by skilled persons (installers).
They are intended to be installed where the prospective short circuit current does not exceed
10 kA unless they are protected by current limiting protective devices with a cut-off current not
exceeding 17 kA.
Enclosures complying with this standard are suitable for use, after installation, at ambient
temperature not normally exceeding 25 °C, but occasionally reaching 35 °C over 24 h, max.
40 °C and min. –5 °C.
An enclosure which is an integral part of an electrical accessory and provides protection
against external influences (e.g. mechanical impacts, ingress of solid objects or of water), is
covered by the relevant standard for such an accessory.
This standard does not apply to a low-voltage switchgear and controlgear assembly
(ASSEMBLY) as defined in the IEC 60439 or IEC 61439 series of standards nor to a main
entrance panel which may or may not be part of the distribution board.
NOTE 1 A main entrance panel is a set composed by a panel or an enclosure equipped with a meter and/or the
main incoming device. Main entrance panels comply with their appropriate standards or the requirements of the
local supplier if any.
NOTE 2 In the following country this standard cannot be used in installations with a 230 V single-phase supply
rated up to 100 A that is under the control of ordinary persons. Integration of mechanical and electrical devices into
an enclosure must be verified by compliance with IEC 60439-3 [British standard EN 60439-3]: UK.
NOTE 3 In the following country this standard can only be used for GP enclosures with the instructions according
to Annex A. For the other types of enclosures the integration of mechanical and electrical devices into an enclosure
is verified by compliance with DS EN 60439-3: DK.
Best Sellers From Electrical Sector
GSO 2530:2016
Gulf Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners

OS GSO 2530:2016
Omani Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners


OS GSO 34:2007
Omani Standard
LEAD-ACID STARTER BATTERIES USED FOR
MOTOR VEHICLES AND INTERNAL
COMBUSTION ENGINES


GSO 34:2007
Gulf Technical Regulation
LEAD-ACID STARTER BATTERIES USED FOR
MOTOR VEHICLES AND INTERNAL
COMBUSTION ENGINES

Recently Published from Electrical Sector
GSO IEC/IEEE 60214-2:2022
IEC/IEEE 60214-2:2019
Gulf Standard
Tap-changers - Part 2: Application guidelines



GSO IEC 60076-22-2:2022
IEC 60076-22-2:2019
Gulf Standard
Power transformers - Part 22-2: Power transformer and reactor fittings - Removable radiators


GSO IEC 60076-7:2022
IEC 60076-7:2018
Gulf Standard
Power transformers - Part 7: Loading guide for mineral-oil-immersed power transformers


GSO IEC 62841-2-4:2022
IEC 62841-2-4:2014
Gulf Standard
Electric motor-operated hand-held tools, transportable tools and lawn and garden machinery - Safety - Part 2-4: Particular requirements for hand-held sanders and polishers other than disc type

